150
Serial communications
ACH550-01 User's Manual
The new settings will take effect when the drive is next powered
up, or when parameter 5127 is activated.
Protocol selection
FBA communication parameters
4
Select EXT FBA with the
UP/DOWN keys and press
SAVE.
5
The assistant recognises
the type of the connected
fieldbus adapter module
and guides you through the
necessary set-up.
If the name of FBA
parameter is not self-
explanatory, the assistant
first tells you which
information is expected
from you.
Code Description
Range
9802
COMM PROT SEL
0…5
Selects the communication protocol.
0 =
NOT
SEL
– No communication protocol selected.
4 =
EXT
FBA
– The drive communicates via a fieldbus adapter module in
option slot 2 of the drive.
• See also parameter
Group 51: EXT COMM MODULE
.
Code Description
Range
5101
FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 =
NOT
DEFINED
– Module not found or not connected. Check chapter
Mechanical installation
in the fieldbus user’s manual and check that
parameter 9802 is set to 4 = EXT FBA.
1 =
Profibus
-
DP
21 =
L
on
W
orks
32 =
CAN
open
37 =
D
evice
N
et
101 =
C
ontrol
N
et
128 =
E
thernet
132 =
PROFINET
135 = E
THER
CAT
136 =
EPL - Ethernet POWERLINK
9802 COMM PROT SEL
PAR EDIT
EXT FBA
[4]
OFF
EXIT
SAVE
00:00
On next screen
set the node number.
EXIT
OK
00:00
ASSISTANT
OFF
5102 FBA PAR 2
PAR EDIT
3
OFF
EXIT
SAVE
00:00