196
Parameter listing and descriptions
ACH550-01 User's Manual
-7 =
DI
1,2(
INV
) – Selects one of three constant speeds (1…3) using
DI
1
and
DI
2.
• Inverse operation uses two digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI
activated):
-8 =
DI
2,3(
INV
) – Selects one of three constant speeds (1…3) using
DI
2
and
DI
3.
• See above (
DI
1,2(
INV
)) for code.
-9 =
DI
3,4(
INV
) – Selects one of three constant speeds (1…3) using
DI
3
and
DI
4.
• See above (
DI
1,2(
INV
)) for code.
-10 =
DI
4,5(
INV
) – Selects one of three constant speeds (1…3) using
DI
4
and
DI
5.
• See above (
DI
1,2(
INV
)) for code.
-11 =
DI
5,6(
INV
) – Selects one of three constant speeds (1…3) using
DI
5
and
DI
6.
• See above (
DI
1,2(
INV
)) for code.
-12 =
DI
1,2,3(
INV
) – Selects one of seven constant speeds (1…7) using
DI
1,
DI
2 and
DI
3.
• Inverse operation uses three digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI
activated):
-13 =
DI
3,4,5(
INV
) – Selects one of seven constant speeds (1…7) using
DI
3,
DI
4 and
DI
5.
• See above (
DI
1,2,3(
INV
)) for code.
-14 =
DI
4,5,6(
INV
) – Selects one of seven constant speeds (1…7) using
DI
4,
DI
5 and
DI
6.
• See above (
DI
1,2,3(
INV
)) for code.
Code Description
Range
DI
1
DI
2 Function
1
1 No constant speed
0
1 Constant speed 1 (1202)
1
0 Constant speed 2 (1203)
0
0 Constant speed 3 (1204)
DI
1
DI
2
DI
3 Function
1
1
1
No constant speed
0
1
1
Constant speed 1 (1202)
1
0
1
Constant speed 2 (1203)
0
0
1
Constant speed 3 (1204)
1
1
0
Constant speed 4 (1205)
0
1
0
Constant speed 5 (1206)
1
0
0
Constant speed 6 (1207)
0
0
0
Constant speed 7 (1208)