Parameter listing and descriptions
285
ACH550-01 User's Manual
4018
ACT1 MINIMUM
-1000…1000%
Sets the minimum value for
ACT
1.
• Scales the source signal used as the actual value
ACT
1 (defined by
parameter 4016
ACT
1
INPUT
). For parameter 4016 values 6 (
COMM
ACT
1) and 7 (
COMM
ACT
2) scaling is not done.
• See the figure: A = Normal; B = Inversion (
ACT
1
MINIMUM
>
ACT
1
MAXIMUM
).
4019
ACT1 MAXIMUM
-1000…1000%
Sets the maximum value for
ACT
1.
• See 4018
ACT
1
MINIMUM
.
4020
ACT2 MINIMUM
-1000…1000%
Sets the minimum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
Code Description
Range
Par 4016
Source
Source min.
Source max.
1
Analogue input 1 1301
MINIMUM
AI
1
1302
MAXIMUM
AI
1
2
Analogue input 2 1304
MINIMUM
AI
2
1305
MAXIMUM
AI
2
3
Current
0
2 · nominal current
4
Torque
-2 · nominal torque
2 · nominal torque
5
Power
-2 · nominal power
2 · nominal power
P 4019
P 4018
P 1301
P 1302
P 1301
P 1302
P 4018
P 4019
ACT
1 (%)
ACT
1 (%)
A
B
Source signal
Source min.
Source max.
Source signal
Source min.
Source max.