Parameter listing and descriptions
319
ACH550-01 User's Manual
2 =
DI
2 – Enables the Interlock function, and assigns a digital input
(starting with
DI
2) to the interlock signal for each PFA relay. These
assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and
1410…1412 with value = 31 (PFA)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
=
0.0, and otherwise enabled).
Code Description
Range
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1: Free
DI
2: Speed Reg Motor
DI
3…
DI
6: Free
Not allowed
1
DI
1: Free
DI
2: Speed Reg Motor
DI
3: First PFA Relay
DI
4…
DI
6: Free
DI
1: Free
DI
2: First PFA Relay
DI
3…
DI
6: Free
2
DI
1: Free
DI
2: Speed Reg Motor
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5…
DI
6: Free
DI
1: Free
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4…
DI
6: Free
3
DI
1: Free
DI
2: Speed Reg Motor
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5: Third PFA Relay
DI
6: Free
DI
1: Free
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5…
DI
6: Free
4
DI
1: Free
DI
2: Speed Reg Motor
DI
3: First PFA Relay
DI
4: Second PFA Relay
DI
5: Third PFA Relay
DI
6: Fourth PFA Relay
DI
1: Free
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5: Fourth PFA Relay
DI
6: Free
5
Not allowed
DI
1: Free
DI
2: First PFA Relay
DI
3: Second PFA Relay
DI
4: Third PFA Relay
DI
5: Fourth PFA Relay
DI
6: Fifth PFA Relay
6
Not allowed
Not allowed
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com