Parameter listing and descriptions
223
ACH550-01 User's Manual
2013
MIN TORQUE SEL
-6…7
Defines control of the selection between two minimum torque limits
(2015
MIN
TORQUE
1 and 2016
MIN
TORQUE
2).
0 =
MIN
TORQUE
1 – Selects 2015
MIN
TORQUE
1 as the minimum limit
used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the
minimum limit used.
• Activating the digital input selects
MIN
TORQUE
2 value.
• De-activating the digital input selects
MIN
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for
selecting the minimum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the minimum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for
selecting the minimum limit used.
• Activating the digital input selects
MIN
TORQUE
1 value.
• De-activating the digital input selects
MIN
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for selecting the minimum limit used.
• See
DI
1(
INV
) above.
2014
MAX TORQUE SEL
-6…7
Defines control of the selection between two maximum torque limits
(2017
MAX
TORQUE
1 and 2018
MAX
TORQUE
2).
0 =
MAX
TORQUE
1 – Selects 2017
MAX
TORQUE
1 as the maximum limit
used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the
maximum limit used.
• Activating the digital input selects
MAX
TORQUE
2 value.
• De-activating the digital input selects
MAX
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for
selecting the maximum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the maximum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input di1 as the control for
selecting the maximum limit used.
• Activating the digital input selects
MAX
TORQUE
1 value.
• De-activating the digital input selects
MAX
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for selecting the maximum limit used.
• See
DI
1(
INV
) above.
2015
MIN TORQUE 1
-600.0…0%
Sets the first minimum limit for torque (%). Value is a percentage of the
motor nominal torque.
Code Description
Range
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com