Parameter listing and descriptions
207
ACH550-01 User's Manual
1502
AO1 CONTENT MIN
-
Sets the minimum
content value.
• Content is the
parameter
selected by
parameter 1501.
• Minimum value
refers to the
minimum content
value that will be
converted to an
analogue output.
• These
parameters
(content and
current min. and
max. settings)
provide scale
and offset
adjustment for
the output. See
the figure.
1503
AO1 CONTENT MAX
-
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be
converted to an analogue output.
1504
MINIMUM AO1
0.0…20.0 mA
Sets the minimum output current.
1505
MAXIMUM AO1
0.0…20.0 mA
Sets the maximum output current.
1506
FILTER AO1
0.0…10.0 s
Defines the filter time constant for
AO
1.
• The filtered signal reaches 63% of a step change within the time
specified.
• See the figure for parameter 1303.
1507
AO2 CONTENT SEL
99…178
Defines the content for analogue output
AO
2. See
AO
1
CONTENT
SEL
above.
1508
AO2 CONTENT MIN
-
Sets the minimum content value. See
AO
1
CONTENT
MIN
above.
Code Description
Range
AO (mA)
AO
CONTENT
P 1504 /
P 1502/1508
P 1503/1509
AO (mA)
AO
CONTENT
P 1505 /
P 1504 /
P 1503/1509
P 1502/1508
P 1505 /
P 1511
P 1510
P 1511
P 1510
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com