356
Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default
Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
1
2
3
4
5
6
40 PROCESS
GAIN
4001
2.5
0.7
0.7
2.5
2.5
2.5
PID SET 1
INTEGRATION
TIME
4002
3.0 s
10.0 s
10.0 s
3.0 s
3.0 s
3.0 s
DERIVATION
TIME
4003
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
PID DERIV
FILTER
4004
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
ERROR
VALUE INV
4005
NO
NO
NO
NO
NO
NO
UNITS
4006
%
%
%
%
%
%
UNIT SCALE
4007
1
1
1
1
1
1
0% VALUE
4008
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
100% VALUE
4009
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
SET POINT
SEL
4010
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
INTERNAL
SETPNT
4011
40.0%
40.0%
40.0%
40.0%
40.0%
40.0%
SETPOINT
MIN
4012
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
SETPOINT
MAX
4013
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
FBK SEL
4014
ACT1
ACT1
ACT1
ACT1
ACT1
ACT1
FBK
MULTIPLIER
4015
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
ACT1 INPUT
4016
AI2
AI2
AI2
AI2
AI2
AI2
ACT2 INPUT
4017
AI2
AI2
AI2
AI2
AI2
AI2
ACT1
MINIMUM
4018
0%
0%
0%
0%
0%
0%
ACT1
MAXIMUM
4019
100%
100%
100%
100%
100%
100%
ACT2
MINIMUM
4020
0%
0%
0%
0%
0%
0%
ACT2
MAXIMUM
4021
100%
100%
100%
100%
100%
100%
SLEEP
SELECTION
4022
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
PID SLEEP
LEVEL
4023
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
PID SLEEP
DELAY
4024
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
WAKE-UP
DEV
4025
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
WAKE-UP
DELAY
4026
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
PID 1 PARAM
SET
4027
SET 1
SET 1
SET 1
SET 1
SET 1
SET 1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com