190
Parameter listing and descriptions
ACH550-01 User's Manual
4 =
AI
2/
JOYST
– Defines analogue input 2 (
AI
2), configured for joystick
operation, as the reference source.
• See above (
AI
1/
JOYST
) description.
5 =
DI
3
U
,4
D
(
R
) – Defines digital inputs as the speed reference source
(motor potentiometer control).
• Digital input
DI
3 increases the speed (the
U
stands for “up”).
• Digital input
DI
4 decreases the speed (the
D
stands for “down”).
• A Stop command resets the reference to zero (the
R
stands for
“reset”).
• Parameter 2205
ACCELER
TIME
2 controls the reference signal’s rate
of change.
6 =
DI
3
U
,4
D
– Same as above (
DI
3
U
,4
D
(
R
)), except:
• A Stop command does not reset the reference to zero. The
reference is stored.
• When the drive restarts, the motor ramps up (at the selected
acceleration rate) to the stored reference.
7 =
DI
5
U
,6
D
– Same as above (
DI
3
U
,4
D
), except that
DI
5 and
DI
6 are the
digital inputs used.
8 =
COMM
– Defines the fieldbus as the reference source.
9 =
COMM
+
AI
1 – Defines a fieldbus and analogue input 1 (
AI
1)
combination as the reference source. See
Analogue input reference
correction
on page
191
.
10 =
COMM
*
AI
1 – Defines a fieldbus and analogue input 1 (
AI
1)
combination as the reference source. See
Analogue input reference
correction
on page
191
.
11 =
DI
3
U
,4
D
(
RNC
) – Same as
DI
3
U
,4
D
(
R
) above, except that:
• Changing the control source (
EXT
1 to
EXT
2,
EXT
2 to
EXT
1,
LOC
to
REM
) does not copy the reference.
12 =
DI
3
U
,4
D
(
NC
) – Same as
DI
3
U
,4
D
above, except that:
• Changing the control source (
EXT
1 to
EXT
2,
EXT
2 to
EXT
1,
LOC
to
REM
) does not copy the reference.
• Stop command resets reference to zero.
13 =
DI
5
U
,6
D
(
NC
) – Same as
DI
3
U
,4
D
above, except that:
• Changing the control source (
EXT
1 to
EXT
2,
EXT
2 to
EXT
1,
LOC
to
REM
) does not copy the reference.
14 =
AI
1+
AI
2 – Defines an analogue input 1 (
AI
1) and analogue input 2
(
AI
2) combination as the reference source. See
Analogue input
reference correction
on page
191
.
15 =
AI
1*
AI
2 – Defines an analogue input 1 (
AI
1) and analogue input 2
(
AI
2) combination as the reference source. See
Analogue input
reference correction
on page
191
.
16 =
AI
1-
AI
2 – Defines an analogue input 1 (
AI
1) and analogue input 2
(
AI
2) combination as the reference source. See
Analogue input
reference correction
on page
191
.
17 =
AI
1/
AI
2 – Defines an analogue input 1 (
AI
1) and analogue input 2
(
AI
2) combination as the reference source. See
Analogue input
reference correction
on page
191
.
Code Description
Range