58
Installing the drive
ACH550-01 User's Manual
4.
On the input power cable, strip the sheathing back far
enough to route individual wires.
5.
On the motor cable, strip the sheathing back far enough to
expose the copper wire shield so that the shield can be
twisted into a bundle (pigtail). Keep the bundle (pigtail) not
longer than five times its width to minimise noise radiation.
360° grounding under the clamp is recommended for the
motor cable to minimise noise radiation. In this case,
remove sheathing at the cable clamp.
6.
Route both cables through the clamps.
7.
Strip and connect the input power and motor wires and the
input power grounding wire to the drive terminals. Frame
size R6: See the figures on page
49
.
8.
Connect the bundle (pigtail) created from the motor cable
shield to the ground (earth).
Note:
Check the cable lengths according to section
Wiring and
EMC considerations
on page
26
.
5
3
4
7
8
7
Tightening
torques
U1, V1, W1,
U2, V2, W2,
N·m lb·ft
R1
1.4
1
R2
1.4
1
R3
2.5
1.8
R4
5.6
4
R5
15
11
R6
40
30
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com