370
Diagnostics and maintenance
ACH550-01 User's Manual
Diagnostics displays
The drive detects error situations and reports them using:
•
green and red LED on the body of the drive
•
status LED on the control panel (if a HVAC control panel is
attached to the drive)
•
control panel display (if a HVAC control panel is attached to
the drive)
•
Fault Word and Alarm Word parameter bits (parameters 0305
to 0309). See
Group 03: FB ACTUAL SIGNALS
.
The form of the display depends on the severity of the error. You
can specify the severity for many errors by directing the drive to:
•
ignore the error situation
•
report the situation as an alarm
•
report the situation as a fault.
Red – faults
The drive signals that it has detected a severe error, or fault, by:
•
enabling the red LED on the drive (LED is either steady or
flashing)
•
showing the steady red status LED on the control panel (if
attached to the drive)
•
setting an appropriate bit in a Fault Word parameter (0305 to
0307)
•
overriding the control panel display with the display of a fault
code
•
stopping the motor (if it was on).
The fault code on the control panel display is temporary.
Pressing any of the following removes the fault message:
MENU, ENTER, UP key or DOWN key. The message reappears
after a few seconds if the control panel is not touched and the
fault is still active.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com