344
Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default
Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
1
2
3
4
5
6
22 ACCEL/
ACC/DEC 1/2
SEL
2201
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
DECEL
ACCELER
TIME 1
2202
30.0 s
15.0 s
15.0 s
30.0 s
10.0 s
5.0 s
DECELER
TIME 1
2203
30.0 s
15.0 s
15.0 s
30.0 s
10.0 s
5.0 s
RAMP SHAPE
1
2204
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
ACCELER
TIME 2
2205
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
DECELER
TIME 2
2206
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
RAMP SHAPE
2
2207
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
EMERG DEC
TIME
2208
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
RAMP INPUT
0
2209
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
23 SPEED
PROP GAIN
2301
5.00
5.00
5.00
5.00
5.00
5.00
CONTROL
INTEGRATION
TIME
2302
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
DERIVATION
TIME
2303
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
ACC
COMPEN-
SATION
2304
0.00 s
0.00 s
0.00 s
0.00 s
0.00 s
0.00 s
AUTOTUNE
RUN
2305
OFF
OFF
OFF
OFF
OFF
OFF
25 CRITICAL
CRIT SPEED
SEL
2501
OFF
OFF
OFF
OFF
OFF
OFF
SPEEDS
CRIT SPEED
1 LO
2502
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
CRIT SPEED
1 HI
2503
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
CRIT SPEED
2 LO
2504
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
CRIT SPEED
2 HI
2505
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
CRIT SPEED
3 LO
2506
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
CRIT SPEED
3 HI
2507
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
0 Hz /
0 rpm
26 MOTOR
FLUX OPT
ENABLE
2601
ON
ON
ON
ON
ON
ON
CONTROLS
FLUX
BRAKING
2602
OFF
OFF
OFF
OFF
OFF
OFF
IR COMP
VOLT
2603
0 V
0 V
0 V
0 V
0 V
0 V
IR COMP
FREQ
2604
80%
80%
80%
80%
80%
80%
U/F RATIO
2605
SQUARED SQUARED SQUARED SQUARED SQUARED SQUARED
SWITCHING
FREQ
2606
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
SWITCH
FREQ CTRL
2607
ON
ON
ON
ON
ON
ON
SLIP COMP
RATIO
2608
0%
0%
0%
0%
0%
0%
NOISE
SMOOTHING
2609
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
DC
STABILIZER
2619
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
OVERMODUL
ATION
2625
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE