358
Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default
Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
1
2
3
4
5
6
41 PROCESS
GAIN
4101
2.5
1.0
1.0
1.0
1.0
1.0
PID SET 2
INTEGRATION
TIME
4102
3.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
DERIVATION
TIME
4103
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
0.0 s
PID DERIV
FILTER
4104
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
ERROR
VALUE INV
4105
NO
NO
NO
NO
NO
NO
UNITS
4106
%
%
%
%
%
%
UNIT SCALE
4107
1
1
1
1
1
1
0% VALUE
4108
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
100% VALUE
4109
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
SET POINT
SEL
4110
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
INTERNAL
SETPNT
4111
40.0%
40.0%
40.0%
40.0%
40.0%
40.0%
SETPOINT
MIN
4112
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
SETPOINT
MAX
4113
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
FBK SEL
4114
ACT1
ACT1
ACT1
ACT1
ACT1
ACT1
FBK
MULTIPLIER
4115
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
ACT1 INPUT
4116
AI2
AI2
AI2
AI2
AI2
AI2
ACT2 INPUT
4117
AI2
AI2
AI2
AI2
AI2
AI2
ACT1
MINIMUM
4118
0%
0%
0%
0%
0%
0%
ACT1
MAXIMUM
4119
100%
100%
100%
100%
100%
100%
ACT2
MINIMUM
4120
0%
0%
0%
0%
0%
0%
ACT2
MAXIMUM
4121
100%
100%
100%
100%
100%
100%
SLEEP
SELECTION
4122
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
PID SLEEP
LEVEL
4123
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
PID SLEEP
DELAY
4124
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
60.0 s
WAKE-UP
DEV
4125
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
WAKE-UP
DELAY
4126
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
0.50 s
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com