8103
REFERENCE STEP 1
0.0…100%
Sets a percentage value that is added to the process reference.
• Applies only when at least one auxiliary (constant speed) motor is
running.
• Default value is 0%.
Example:
An ACH550 operates three parallel pumps that maintain
water pressure in a pipe.
• 4011
INTERNAL
SETPNT
sets a constant pressure reference that
controls the pressure in the pipe.
• The speed regulated pump operates alone at low water consumption
levels.
• As water consumption increases, the first auxiliary (constant speed)
pump starts to operate, then the second one.
• As flow increases, the pressure at the output end of the pipe drops
relative to the pressure measured at the input end. As auxiliary
motors step in to increase the flow, the adjustments below correct the
reference to more closely match the output pressure.
• When the first auxiliary pump operates, increase the reference with
parameter 8103
REFERENCE
STEP
1.
• When two auxiliary pumps operate, increase the reference with
parameter 8103
REFERENCE
STEP
1 + parameter 8104
REFERENCE
STEP
2.
• When three auxiliary pumps operate, increase the reference with
parameter 8103
REFERENCE
STEP
1 + parameter 8104
REFERENCE
STEP
2 + parameter 8105
REFERENCE
STEP
3.
8104
REFERENCE STEP 2
0.0…100%
Sets a percentage value that is added to the process reference.
• Applies only when at least two auxiliary (constant speed) motors are
running.
• See parameter 8103
REFERENCE
STEP
1.
8105
REFERENCE STEP 3
0.0…100%
Sets a percentage value that is added to the process reference.
• Applies only when at least three auxiliary (constant speed) motors are
running.
• See parameter 8103
REFERENCE
STEP
1.