Serial communications
143
ACH550-01 User's Manual
(3AFE68320658 [English]) and
BACnet® Protocol
(3AUA0000004591 [English]).
The communication between the drive and the fieldbus is then
activated by selecting the appropriate protocol with parameter
9802
COMM
PROT
SEL
. After the communication is initialized, the
configuration parameters become available in parameter
Group
53: EFB PROTOCOL
in the drive.
Setting up EFB with the Serial Communication assistant is
shown below. The related parameters are described starting
from page
144
.
For BACnet/IP, follow the instructions in
RBIP-01 BACnet/IP
Router Module Installation Manual
(3AUA0000040168 [English])
and
RBIP-01 BACnet/IP Router Module User’s Manual
(3AUA0000040159 [English]).
Setting up EFB with the Serial Communication assistant
To set up EFB, follow these steps:
1
Press MENU to go to the
main menu.
2
Select ASSISTANTS with
the UP/DOWN keys and
press ENTER.
3
Scroll to Serial
Communication and press
SEL.
4
Select the protocol with the
UP/DOWN keys and press
SAVE.
0 A
0 Hz
0 %
0.
0.
0.
0.0Hz
OFF
MENU
00:00
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT
ENTER
00:00
OFF
MAIN MENU
2
Low Noise Set-up
Panel Display
Timed Functions
Outputs
Serial Communication
EXIT
SEL
00:00
ASSISTANTS
14
OFF
9802 COMM PROT SEL
PAR EDIT
BACNET
[5]
OFF
EXIT
SAVE
00:00