396
Technical data
ACH550-01 User's Manual
IEC ratings, 380…480 V drives
Type
Valid up to 40 °C
Frame
size
ACH550-01-
I
2N
A
P
N
kW
Max.
current
I
MAX
Three-phase supply voltage, 380…480 V
02A4-4
2.4
0.75
3.1
R1
03A3-4
3.3
1.1
4.3
R1
04A1-4
4.1
1.5
5.9
R1
05A4-4
5.4
2.2
7.4
R1
06A9-4
6.9
3.0
9.7
R1
08A8-4
8.8
4.0
12.4
R1
012A-4
11.9
5.5
15.8
R1
015A-4
15.4
7.5
21.4
R2
023A-4
23
11
27.7
R2
031A-4
31
15
41
R3
038A-4
38
18.5
56
R3
045A-4
45
22
68
R3
059A-4
59
30
79
R4
072A-4
72
37
106
R4
087A-4
87
45
139
R4
125A-4
125
55
173
R5
157A-4
157
75
223
R6
180A-4
180
90
281
R6
195A-4
205
110
324
R6
246A-4
246
132
346
R6
290A-4
290
160
441
R6
00467918.xls C
I
MAX
: Maximum output current allowed for 2 seconds every minute
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com