Parameter listing and descriptions
173
ACH550-01 User's Manual
0113
CTRL LOCATION
0=HAND, 1=EXT1,
2=EXT2
Active control location. Alternatives are:
0 =
HAND
1 =
EXT
1
2 =
EXT
2
0114
RUN TIME (R)
0…9999 h
Drive’s accumulated running time in hours (h)
• Can be
reset
by pressing the UP and DOWN keys simultaneously
when in the Parameters mode.
0115
KWH COUNTER (R)
0…65535 kWh
Drive’s accumulated power consumption in kilowatt hours
The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0.
• The counter can be
reset
by pressing the UP and DOWN keys
simultaneously when in the Parameters mode.
0116
APPL BLK OUTPUT
0…100%
(0…600% for torque)
Application block output signal. Value is from either:
• PFA control, if PFA Control is active, or
• parameter 0112
EXTERNAL
REF
2.
0118
DI 1-3 STATUS
000…111 (0…7 decimal)
Status of the three digital inputs
• Status is displayed as a binary number.
• 1 indicates that the input is activated.
• 0 indicates that the input is deactivated.
0119
DI 4-6 STATUS
000…111 (0…7 decimal)
Status of the three digital inputs
• See parameter 0118
DI
1-3
STATUS
.
0120
AI 1 0…100%
Relative value of analogue input 1 in %
0121
AI 2
0…100%
Relative value of analogue input 2 in %
Code Description
Range
DI
1
DI
2
DI
3