348
Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default
Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
1
2
3
4
5
6
31 AUTOMATIC
NUMBER OF
TRIALS
3101
5
5
5
5
5
5
RESET
TRIAL TIME
3102
30.0 s
30.0 s
30.0 s
30.0 s
30.0 s
30.0 s
DELAY TIME
3103
6.0 s
6.0 s
6.0 s
6.0 s
6.0 s
6.0 s
AR OVER-
CURRENT
3104
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
DISABLE
AR OVER-
VOLTAGE
3105
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
AR UNDER-
VOLTAGE
3106
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
AR AI<MIN
3107
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
AR
EXTERNAL
FLT
3108
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
32 SUPER-
SUPERV 1
PARAM
3201
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
VISION
SUPERV 1
LIM LO
3202
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
SUPERV 1
LIM HI
3203
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
50.0 Hz
SUPERV 2
PARAM
3204
CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
SUPERV 2
LIM LO
3205
-
-
-
-
-
-
SUPERV 2
LIM HI
3206
-
-
-
-
-
-
SUPERV 3
PARAM
3207
TORQUE
TORQUE
TORQUE
TORQUE
TORQUE
TORQUE
SUPERV 3
LIM LO
3208
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
SUPERV 3
LIM HI
3209
100.0%
100.0%
100.0%
100.0%
100.0%
100.0%
33 INFOR-
FIRMWARE
3301
Firmware
version
Firmware
version
Firmware
version
Firmware
version
Firmware
version
Firmware
version
MATION
LOADING
PACKAGE
3302
0
0
0
0
0
0
TEST DATE
3303
0
0
0
0
0
0
DRIVE
RATING
3304
-
-
-
-
-
-
PARAMETER
TABLE
3305
Par. table
version
Par. table
version
Par. table
version
Par. table
version
Par. table
version
Par. table
version
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com