Serial communications
157
ACH550-01 User's Manual
System control inputs
1505
MAXIMUM AO1
0.0…20.0 mA
Sets the maximum output current.
1506
FILTER AO1
0.0…10.0 s
Defines the filter time constant for
AO
1.
• The filtered signal reaches 63% of a step change within the time
specified.
• See the figure for parameter 1303 in chapter
Parameter listing and
descriptions
.
1507
AO2 CONTENT SEL
99…178
Defines the content for analogue output
AO
2. See
AO
1
CONTENT
SEL
above.
1508
AO2 CONTENT MIN
-
Sets the minimum content value. See
AO
1
CONTENT
MIN
above.
1509
AO2 CONTENT MAX
-
Sets the maximum content value. See
AO
1
CONTENT
MAX
above.
1510
MINIMUM AO2
0…20.0 mA
Sets the minimum output current. See
MINIMUM
AO
1 above.
1511
MAXIMUM AO2
0…20.0 mA
Sets the maximum output current. See
MAXIMUM
AO
1 above.
1512
FILTER AO2
0…10.0 s
Defines the filter time constant for AO2. See
FILTER
AO
1 above.
Code Setting for fieldbus control & description Range
1601
RUN ENABLE
-6…7
Selects the source of the Run enable signal. See the figure on page
214
.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the
Run enable signal.
• Bit 6 of Command Word 1 (parameter 0301) activates the Run
disable signal.
• See the fieldbus user’s manual for detailed instructions.
Note:
Hardware is bypassed if a command word is the source of the
Run enable signal.
1604
FAULT RESET SEL
-6…8
Selects the source for the fault reset signal. The signal resets the drive
after a fault trip if the cause of the fault no longer exists.
8 =
COMM
– Defines the fieldbus as a fault reset source.
• The Command Word is supplied through fieldbus communication.
• The bit 4 of Command Word 1 (parameter 0301) resets the drive.