212
Parameter listing and descriptions
ACH550-01 User's Manual
1606
LOCAL LOCK
-6…8
Defines control for the use of the HAND mode. The HAND mode allows
drive control from the control panel (operator keypad).
• When
LOCAL
LOCK
is active, the control panel cannot change from
the AUTO mode to the HAND mode.
0 =
NOT
SEL
– Disables the lock. The control panel can select HAND and
control the drive.
Note:
The OFF key always stops the drive, regardless of the parameter
1606
LOCAL
LOCK
value.
If
LOCAL
LOCK
is active and the drive is in the AUTO mode when the
OFF key is pressed, the drive remains in the AUTO mode but coasts
to stop and shows alarm 2017
OFF
BUTTON
on the control panel
display. (This alarm is shown on the control panel only; it is not
indicated by relay outputs.) Press the AUTO key to restart the drive.
Note:
If the drive is in the OFF or HAND mode and
LOCAL
LOCK
is
activated (e.g. from the control panel or through a digital input),
control from the control panel is still possible until the drive is set to
the AUTO mode. It is not until then that
LOCAL
LOCK
becomes
effective, disabling changing from from the AUTO mode to the OFF or
HAND mode by pressing the OFF or HAND key.
1 =
DI
1 – Defines digital input
DI
1 as the control for setting the local lock.
• Activating the digital input locks out local control.
• De-activating the digital input enables the HAND selection.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for setting
the local lock.
• See
DI
1 above.
7 =
ON
– Sets the lock. The control panel cannot select HAND, and
cannot control the drive.
8 =
COMM
– Defines bit 14 of Command Word 1 (parameter 0301) as the
control for setting the local lock.
• The Command Word is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for
setting the local lock.
• De-activating the digital input locks out local control.
• Activating the digital input enables the HAND selection.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for setting the local lock.
• See
DI
1(
INV
) above.
Code Description
Range
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com