Group 15: ANALOGUE OUTPUTS
This group defines the drive’s analogue (current signal) outputs.
The drive’s analogue outputs can be:
•
any parameter of
Group 01: OPERATING DATA
•
limited to programmable minimum and maximum values of
output current
•
scaled (and/or inverted) by defining the minimum and
maximum values of the source parameter (or content).
Defining a maximum value (parameter 1503 or 1509) that is
less than the content minimum value (parameter 1502 or
1508) results in an inverted output.
•
filtered.
Code Description
Range
1501
AO1 CONTENT SEL
99…178
Defines the content for analogue output AO1.
99 =
EXCITE
PTC
– Provides a current source for sensor type PTC.
Output = 1.6 mA. See
Group 35: MOTOR TEMP MEAS
.
100 =
EXCITE
PT
100 – Provides a current source for sensor type PT100.
Output = 9.1 mA. See
Group 35: MOTOR TEMP MEAS
.
101…178 – Output corresponds to a parameter in
Group 01:
OPERATING DATA
.
• Parameter defined by value (e.g. value 102 = parameter 0102)