Technical data
403
ACH550-01 User's Manual
Fuses, 208…240 V drives
Note:
The use of ultra rapid fuses is recommended, but normal
HRC fuses, ABB Tmax moulded case circuit breakers (MCCB)
or ABB S200 B/C miniature circuit breakers (MCB) are sufficient.
See section
Circuit breakers
on page
404
.
ACH550-01-
Input
current
A
Mains fuses
IE 60269 gG
A
UL class T
A
Bussmann
type
1
04A6-2
4.6
10
10
JJS-10
06A6-2
6.6
07A5-2
7.5
012A-2
11.8
16
15
JJS-15
017A-2
16.7
25
25
JJS-25
024A-2
24.2
30
JJS-30
031A-2
30.8
40
40
JJS-40
046A-2
46
63
60
JJS-60
059A-2
59
80
JJS-80
075A-2
75
80
100
JJS-100
088A-2
88
100
110
JJS-110
114A-2
114
125
150
JJS-150
143A-2
143
200
200
JJS-200
178A-2
178
250
250
JJS-250
221A-2
221
315
300
JJS-300
248A-2
248
350
JJS-350
00467918.xls C
1
Example
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com