60
Installing the drive
ACH550-01 User's Manual
3.
Route the control cable(s) through the clamp(s) and tighten
the clamp(s).
4.
Connect the ground (earth) shield for digital and analogue I/
O cables at X1:1.
5.
Strip and connect the individual control wires to the drive
terminals. See chapter
Application macros and wiring
.
6.
Install the connection box cover (one screw).
WARNING!
All ELV (Extra Low Voltage) circuits connected to the
drive must be used within a zone of equipotential bonding, i.e.
within a zone where all simultaneously accessible conductive parts
are electrically connected to prevent hazardous voltages appearing
between them. This is accomplished by a proper factory grounding.
For completing the connections, go to chapter
Application
macros and wiring
.
3
4
5
Tightening
torque:
0.4 N·m (0.3 lb·ft)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com