Installation situations
Supporting con-
struction
Installation location
Minimum
thickness
[mm]
Class of per-
formance EI TT
(v
e
–h
o
, i ↔ o) S
up to
Installation
type
Installa-
tion
informa-
tion
in, combined assembly
94
EI 90 S
N
1
in, without installation kit
94
EI 60 S
T
in, installation kit TQ / TQ2
94
EI 120 S
E
1
94
EI 90 S
E
1
80
EI 60 S
E
1
75
EI 30 S
E
remote from, installation kit
WE / WE2
94
EI 90 S
E
remote from, mineral wool insu-
lation
130
EI 60 S
T
in, direct installation, installation
kit GL / GL2
94
EI 90 S
T
in, flexible ceiling joint, installa-
tion kit GL / GL2
100
EI 90 S
E
in, fire batt
94
EI 120 S
W
1
94
EI 90 S
W
1
80
EI 60 S
W
1
75
EI 30 S
W
1
in, combined penetration seal
100
EI 90 S
W
1
in, fire protection block bulk-
head
100 – 200
EI 90 S
T
Timber stud walls
in
130
EI 120 S
N
130
EI 90 S
N
110
EI 60 S
N
105
EI 30 S
N
in, installation kit TQ / TQ2
130
EI 120 S
E
110
EI 60 S
E
105
EI 30 S
E
remote from, mineral wool insu-
lation
130
EI 60 S
T
in, fire batt
130
EI 120 S
W
130
EI 90 S
W
110
EI 60 S
W
105
EI 30 S
W
1)
The class of performance depends on the installation details
2)
Thickness increased near the installation opening
3)
Cadolto system
4)
Depending on local conditions
N = Mortar-based installation
E = Installation kit
W = Fire batt
E = Dry mortarless installation
Installation
Installation situations
Fire damper Type FKRS-EU
19