Fig. 68: Dry mortarless installation with installation kit GL / GL2 into lightweight partition or compartment wall
1
FKRS-EU
2.12
Installation kit GL / GL2
3.2
Lightweight partition wall or compartment wall
with metal support structure, cladding on both
sides
4.1
Solid ceiling slab
5.7
Anchor bolt Hilti
®
HUS-6 or equivalent wallplugs
with fire protection suitability certificate, adapted
to the particular building material, alternatively
push through installation
6.27
Holding plate on both sides, 90
×
140
×
1.5 mm
Up to EI 90 S
Note:
Do not make any screw connections in the hatched area.
Additional requirements: dry mortarless installation with installation kit GL / GL2 into lightweight partition
and compartment walls
Lightweight partition wall or compartment wall, see
Installation kit GL / GL2, see
Wall thickness W = 100 – 235 mm
50 – 230 mm distance from the fire damper to the ceiling slab
≥
125 mm distance from the fire damper to adjacent walls
≥ 200 mm distance between two fire dampers, distance = 100 mm when installed in the same installation
opening
Subsidence of the ceiling slab a
≤
40 mm
Installation only under solid ceiling slabs without cavities
Note:
For installation, follow the supplied installation manual.
Installation
Lightweight partition walls and compartment wall... > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
83