5.3.1.5
Installation kit WE / WE2
Installation kit WE / WE2 for installation remote from solid walls and ceiling slabs as well as remote from
lightweight partition walls
The installation kit WE is an integral component of the fire damper and must be ordered together with the
damper.
The installation kit WE2 is supplied separately and must be installed by the customer.
The installation kit can also be supplied subsequently and mounted on the fire damper.
Fig. 25: Supply package and installation of installation kit WE2 for dry mortarless installation
1
FKRS-EU
2.6
Installation kit WE2, consisting of:
a
Half-shell 1
b
Half-shell 2
c
Bracket
d
Sheet metal cover plate with Kerafix sealing tape
e
Dry wall screw
Installation of installation kit WE2
1.
Lay half-shells (2.6a) and (2.6b) of the installation kit (2.6) around the FKRS-EU and fix with two brackets
(2.6c) (installation position of the FKRS-EU as required).
2.
On the rear of the installation kit (2.6), fix the sheet metal cover plate (2.6d) with 4 dry wall screws (2.6e).
Installation
General installation information > Installation block and installation kits
Fire damper Type FKRS-EU
38
Содержание FKRS-EU