2.2 FKRS-EU with fusible link
Dimensions and weight
Fig. 2: FKRS-EU with fusible link
1
Keep clear to provide access for operation
A Installation side
B Operating side
Connecting cable length / cross section
1 m / 3 × 0.34 mm²
Protection level
IP 66
Type of contact
1 changeover contact, gold-plated
Maximum switching current
0.5 A
Maximum switching voltage
30 V DC, 250 V AC
Contact resistance
approx. 30 mΩ
Weight [kg]
Nominal size [mm]
Æ
DN [mm]
100
99
125
124
150
149
160
159
180
179
200
199
224
223
250
249
280
279
315
314
FKRS-EU with fusible link
1.3
1.6
1.8
2.0
2.3
2.5
2.7
3.3
3.8
4.4
... and installation block ER
5.7
8.6
7.6
7.3
11.0
9.8
13.5
12.1
16.0
15.0
... and installation kit TQ / TQ2
5.4
6.1
7.0
7.9
8.8
9.7
10.6
12.0
13.7
15.8
... and installation kit WA / WA2
4.4
5.2
6.1
6.6
7.4
8.2
9.0
10.2
11.7
13.6
... and installation kit WE / WE2
4.4
5.2
6.1
6.6
7.4
8.2
9.0
10.2
11.7
13.6
... and installation kit GL / GL2
4.4
5.2
6.1
6.6
7.4
8.2
9.0
10.2
11.7
13.6
Technical data
FKRS-EU with fusible link
Fire damper Type FKRS-EU
11
Содержание FKRS-EU
Страница 176: ...Fire damper Type FKRS EU 176...