Installation into combined penetration seal
Mixed installation of fire dampers FK-EU and FKRS-
EU together with cables and tubes in a fire batt
system: Hilti-CFS-CT, CP 670 and CP 673.
Installation is in solid walls, lightweight partition
walls with metal or timber support structure and
solid wood / cross-laminated timber.
The maximum penetration seal dimensions
B1
×
H1 = 3000
×
2000 mm.
The penetration seal size depends on the configura-
tion, see the separate installation and operating
manual for the combined penetration seal.
The minimum distance between the casings of the
FKRS-EU is
≥
40 mm.
The minimum distance between fire damper casing
and cable penetrations is
≥
100 mm.
The minimum distance between fire damper casing
and pipe penetrations is
≥
50 mm.
Distance from FKRS-EU to fire dampers FK-EU
≥
50 mm.
The position of the fire dampers, tubes and cable in
the combined penetration seal is irrelevant, but must
comply with the specified minimum distances.
Fire dampers, cable, cable bundles, cable trays,
conduits and plastic pipes can be laid individually or
in multiples.
The fire dampers must be suspended on both sides,
Fig. 18: Combined penetration seal
1a
FKRS-EU with ablative coating around the perim-
eter, thickness = min. 2.5 mm
Alternatively:
- Mineral wool > 1000 °C,
> 80 kg/m³, thickness = 20 mm
- Sleeve (can be ordered separately)
- Elastomeric foam (flame-resistant, non-dripping,
)
1b
FK-EU
2.4
Fire batt with ablative coating
3.2
Solid wall, lightweight partition wall with metal or
timber support structure (cladding on both sides),
solid wood or cross-laminated timber
6.5
Mineral wool (depending on wall construction)
7.10 Trim panels
7.13 Cladding, fire-resistant, also with sheet steel insert
11.1 Cable tray
11.2 Cable set
11.3 Pipe collar
11.6 Cable penetration
If this fire damper is used in Germany:
Use in the combined penetration seal in Germany
requires official approval by others.
Hilti provides additional information on cable and
pipe penetrations and the fire batt system.
Note:
Further information about the combined penetra-
tion seal is provided in the installation and operating
manual for the combined penetration seal.
Installation
General installation information
Fire damper Type FKRS-EU