Fig. 129: Mortar-based installation into wooden beam / laminated beam ceiling, suspended (illustration representa-
tive, alternative ceiling construction possible on request)
1
FKRS-EU
2.1
Mortar
6.5
Mineral wool fill if required
7.11
Trim panel, same construction as 7.19
7.15
Wood sheet, at least 600 kg/³
7.16
Wooden beam / gluelam min. 100
×
80 mm
(reduce distances between wooden beams to the
size of the installation opening)
7.17
Trimmers, wooden beam / gluelam
min. 100
×
80 mm
7.19
Fire-resistant cladding (ceiling-dependent)
Up to EI 90 S
Up to EI 60 S
EI 30 S
Additional requirements: mortar-based installation into wooden beam / laminated beam ceilings
Wooden beam ceiling, see
≥
75 mm distance from fire damper to load-bearing structural elements
≥
200 mm distance between two fire dampers in separate installation openings
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Wooden beam ceilings > Mortar-based installation into wooden beam cei...
Fire damper Type FKRS-EU
149