Additional requirements: installation with installation kit WE / WE2 remote from solid walls with
wall penetration
Solid wall
Installation kit WE / WE2, see
Suspension and fixing, see
≥
130 mm distance from the fire damper to the wall or ceiling slab
≥
200 mm distance between two fire dampers (wall penetration through separate wall openings)
Note:
For more installation details and for components to be provided by others, see the WE / WE2 installation
manual.
Installation
Solid walls > Installation with installation kit WE / WE2 re...
Fire damper Type FKRS-EU
57