5.8.3 Dry mortarless installation with installation kit WA / WA2
Fig. 102: Dry mortarless installation with installation kit WA / WA2 into a shaft wall with metal support structure
1
FKRS-EU
2.5
Installation kit WA / WA2
3.7
Shaft wall with metal support structure, cladding
on one side
5.4
Threaded rod (M8 or M10) as push through
installation with washers and nuts
7.14
Reinforcing board (square, DN + 100 mm), cal-
cium silicate, thickness = 30 – 50 mm or mineral
wool,
≥
1000 °C,
≥
140 kg/m³,
thickness = 50 mm
7.19
Fire-resistant cladding (fire-rated plasterboard
panel, thickness
≥
12.5 mm)
8.3
PROMATECT®-LS board, d = 35 mm
9.2
Extension piece or duct
Up to EI 90 S
Additional requirements: dry mortarless installation with installation kit WA / WA2 into shaft walls with metal
support structure
Installation kit WA / WA2, see
≥
75 mm distance from fire damper to load-bearing structural elements
≥
200 mm distance between two fire dampers
1.
Make a circular installation opening DN + approx. 5 mm between two regular studs.
2.
Create a reinforcing board (7.14) and fix it to the installation kit.
3.
Create Promatect strips (8.3).
4.
Push the fire damper into the wall opening and fix it with threaded rods (5.4) and Promatect strips (8.3).
5.
Apply fire-resistant cladding (7.19).
Installation
Shaft walls with metal support structure > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
120