6.19
Mineral wool > 1000 °C, > 80 kg/m³,
thickness = 20 mm, panel material around the
perimeter, leave out the actuator and release
mechanism; inspection openings must remain
accessible
6.20
Sleeve (can be ordered separately)
–
See table
Lightweight partition wall with timber support structure
NW
[mm]
Fire resistance prop-
erties
to
Coating
s2
[mm]
Detail
Installation side
A
Operating side
B
100 – 200
EI 90 S
–
–
10 – 600
,
100 – 315
EI 90 S
–
x
10 – 600
,
100 – 200
EI 120 S
–
x
40 – 600
,
100 – 315
EI 120 S
x
x
40 – 600
,
100 – 315
EI 30 S
–
–
10 – 600
,
Additional requirements: dry mortarless installation with fire batt into lightweight partition walls with timber
support structure
Timber support structure or half-timbered construction, see
Fire batt systems, installation details, distances / dimensions, see
f
Suspension and fixing, see
Installation
Lightweight partition walls with timber support ... > Dry mortarless installation with fire batt