background image

1

01/19

FOK-EIS-180  Fire dampers CE

EN 15650:2010

 

M A D E L

  

â

 

European Test Standard, EN 1366-2

(Fire resistance tests for service installations 

Part 2: Fire dampers)

European Classification  Standard, EN 13501-3

(Fire classification of construction products and building 

elements 

Part 3: Classification using data from fire resistance tests on 
products and elements used in building service installations: 

fire resisting ducts and fire dampers

)

European Standard for CE Marking, EN 15650

(Ventilation for buildings. Fire dampers)

European Test Standard, EN 60529:1991

(Degrees of protection provided by enclosures (IP Code))

European Test Standard EN 1751

(Ventilation for buildings 

– Air terminal devices –

Aerodynamic testing of dampers and valves)

International  Test Standard ISO 10294-4

(Fire resistance tests 

– Fire dampers for air distribution systems

Part 4: Test of thermal release mechanism)

• The fire dampers 

FOK-EIS-180

work as a separator 

between two sectors of fire and ensure the same fire 
resistance that the structural elements of 
compartmentalisation, which limits the risk of spreading 
of fire by interior of the building. 

• FOK-EIS-180 fire dampers are according with the 
following standards:

• The casing is made of galvanised steel, and joined by 
clinching system (cold forming the material).

• It incorporates a solid perimeter frame to facilitate the 
sealing between the fire damper and support 
construction. 

• The housing is made   from galvanized steel. It has a 
symmetrical design that allows wall mounting 
regardless of air flow.

• The blade is made   of ceramic material resistant to 
high temperatures and abrasion.

•These dampers meet the conditions required for the 
symbol (S) to cold smoke seal.

• The airtightness to the passage of cold smoke is 
achieved through a joint between the perimeter of the 
housing and the blade.

• For high temperatures, the damper is equipped with 
an expanding intumescent seal, forming a paste that 
prevents the passage of hot air and smoke from one 
side of the damper to another.

• The operating devices of the dampers is automatic 
shooting by means of a thermal fuse calibrated at 72

°

to activate the closure when reaches that temperature. 
Reset is manual except for motorized dampers.

Содержание FOK-EIS-180

Страница 1: ...the structural elements of compartmentalisation which limits the risk of spreading of fire by interior of the building FOK EIS 180 fire dampers are according with the following standards The casing is...

Страница 2: ...mm Built in 0 180 EI 180 ve i o S 500Pa Rigid floor Hormig n armado 200 mm Built in 0 360 EI 180 ve i o S 300Pa Sensing element load bearing capacity Sensing element response temperature Closure time...

Страница 3: ...B mm C mm MFS 115 121 32 MFS 115 121 32 MFS 191 121 40 MFB 150 121 25 MFB 160 121 32 S dim FOK EIS 180 Rectangular damper 90 angled flange connection to the ducts MA Manual resetting damper Is not ne...

Страница 4: ...pen resetting Manual Turning counterclockwise 90 the manual resetting axe using a tool with a smaller diameter than 8mm C Automatic Electrical connection Switches normally closed contacts COM NF NO CO...

Страница 5: ...esetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Position damper indicator Closed switches IP54 Protection 72 C A...

Страница 6: ...h allen key D To keep the blade open lock by manual lock Automatic By supplying the power supply E Electrical connection Fixed switching points at 5 and 80 Fixed switching point at 5 to contact A Fixe...

Страница 7: ...tallation regarding this document the fire damper will not comply the classification Install the fire damper with the blade closed and avoid excessive pressures in its casing Avoid to project material...

Страница 8: ...supporting construction sealing Dimensions Supporting construction Sealing Classification 200 x 200 to 1000 x 600 Rigid wall Brick wall 110mm Mortar EI180 ve i o S 300Pa 200 x 200 to 1000 x 600 Rigid...

Страница 9: ...ETAIL A 144 144 1 Operating device position 2 Support construction opening Hnominal 150 20 Lnominal 150 20 Starting plane of supporting construction sealing Dimensions Supporting construction Sealing...

Страница 10: ...amper classed EIS 180 in accordance to the European Standard EN 13501 3 and certified CE according to EN 15650 series FOK EIS 180 MFS230V dim 500 x 300 Operated by means of a motorized operating devic...

Страница 11: ...615 0 209 6 0 525 5 1 0 5 0 358 0 410 0 75 0 444 0 399 0 4 2 5 0 495 0 59 0 270 3 75 0 480 0 58 0 303 3 0 470 800 0 855 9 5 0 088 700 0 865 10 25 0 077 600 0 845 8 75 0 1 900 1000 0 830 8 0 111 Dpt P...

Страница 12: ...3500 6500 8000 4 5 6 7 8 9 0 4 0 2 Kr 1 0 8 0 6 10 2 35 40 45 50 L wa1 dB A 1 1 5 3 4 2 Vf m s 1 5 2 3 4 5 6 7 8 9 10 0 15 0 02 DPt Pa 30 15 20 10 100 60 80 40 0 06 0 05 0 03 0 04 0 08 0 1 0 8 A free...

Отзывы: