background image

1.

Actuator

2.

Position damper indicator

3.

Manual resetting

4.

Manual lock

5.

Plug closed switches cable

6.

Thermoelectrical fuse cable

7.

Power supply cable

8.

Thermoelectrical fuse 72ºC

9.

Manual test switch

10.

LED status fusible indicator

2

1

8

4

3

5

7

6

10

9

fig. MFS

…V

Close (unlocking)

Manual: 

Pressing the manual test switch 

(A)

Remote: 

By interrupting  the power supply 

(B)

Automatic: 

The fusible link reaches 72ºC 

(C)

Open (resetting)

Manual: 

Turning  counterclockwise  the manual resetting with allen key 

(D)

To keep the blade open, lock by manual lock

Automatic: 

By supplying  the power supply 

(E)

Electrical connection

• Fixed switching points at 5º and 80º

•• Fixed switching point at 5º to contact “A”

•• Fixed switching point at 80º to contact “B”

S1

S2

S3

S4

S5

S6

S1

S2

S3

S4

S5

S6

A. CLOSED DAMPER

CONTACT 

“B”

CONTACT 

“A”

B. OPEN DAMPER

CONTACT 

“B”

CONTACT 

“A”

5

01/19

OPERATING DEVICES

…- /MFS…/

Damper operated by remote control by means of an

actuator with switch off device at 24 or 230V or a
thermal fuse calibrated at 72 

°

C. . 

Standard:

- Internal  and external  thermoelectrical fuse  72ºC
- Automatic resetting
- Automatic closing by fuse  72ºC
- Remote  closing by interruption  of power   supply
- Manual  test switch
- LED status  fusible  indicator
- Position  damper  indicator 
- Closed  switches
- IP54 Protection

72ºC

A

B

C

D

E

AUXILIARY SWITCHES CABLE

MEANING

COLOR

Switch "A" input

S1

grey/ red

Switch "A" normally-closed contact

S2

grey/ blue

Switch "A" normally-open contact

S3

grey/ pink

Switch "B" input

S4

black/ red

Switch "B" normally-closed contact

S5

black/ blue

Switch "B" normally-open contact

S6

black/ pink

ACTUATOR 24VCA/24

…48VCC

MEANING

COLOR

System potential 24VCA/ 24

…48VCC

1

red

System neutral

2

black

ACTUATOR 230VCA

MEANING

COLOR

Line 230VCA

3

Brown

Neutral

4

Blue

200

250

300

350

400

450

500

550

600

650

700

750

800

850

900

950

1000

1050

1100

1150

1200

1250

1300

1350

1400

1450

1500

200

250

300

350

400

450

500

550

600

650

700

750

800

L

H

Reference

a/size

Torque

Voltage

Consumption

Time 

Open/ Close

MFS24V

4 Nm

CA 24V, CC 24/48V

3,5W  (running)/ 2W  (stationary)

90s/ 15s

MFS230V

4 Nm

CA 230V

4,5W  (running)/ 3,5W  (stationary)

90s/ 15s

MFS24V

7 Nm

CA 24V, CC 24/48V

3,5W  (running)/ 2W  (stationary)

90s/ 15s

MFS230V

7 Nm

CA 230V

4,5W  (running)/ 3,5W  (stationary)

90s/ 15s

MFS24V

18 Nm

CA 24V, CC 24/48V

5W (running)/ 4W  (stationary)

90s/ 15s

MFS230V

18 Nm

CA 230V

6W  (running)/ 4W  (stationary)

90s/ 15s

Содержание FOK-EIS-180

Страница 1: ...the structural elements of compartmentalisation which limits the risk of spreading of fire by interior of the building FOK EIS 180 fire dampers are according with the following standards The casing is...

Страница 2: ...mm Built in 0 180 EI 180 ve i o S 500Pa Rigid floor Hormig n armado 200 mm Built in 0 360 EI 180 ve i o S 300Pa Sensing element load bearing capacity Sensing element response temperature Closure time...

Страница 3: ...B mm C mm MFS 115 121 32 MFS 115 121 32 MFS 191 121 40 MFB 150 121 25 MFB 160 121 32 S dim FOK EIS 180 Rectangular damper 90 angled flange connection to the ducts MA Manual resetting damper Is not ne...

Страница 4: ...pen resetting Manual Turning counterclockwise 90 the manual resetting axe using a tool with a smaller diameter than 8mm C Automatic Electrical connection Switches normally closed contacts COM NF NO CO...

Страница 5: ...esetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Position damper indicator Closed switches IP54 Protection 72 C A...

Страница 6: ...h allen key D To keep the blade open lock by manual lock Automatic By supplying the power supply E Electrical connection Fixed switching points at 5 and 80 Fixed switching point at 5 to contact A Fixe...

Страница 7: ...tallation regarding this document the fire damper will not comply the classification Install the fire damper with the blade closed and avoid excessive pressures in its casing Avoid to project material...

Страница 8: ...supporting construction sealing Dimensions Supporting construction Sealing Classification 200 x 200 to 1000 x 600 Rigid wall Brick wall 110mm Mortar EI180 ve i o S 300Pa 200 x 200 to 1000 x 600 Rigid...

Страница 9: ...ETAIL A 144 144 1 Operating device position 2 Support construction opening Hnominal 150 20 Lnominal 150 20 Starting plane of supporting construction sealing Dimensions Supporting construction Sealing...

Страница 10: ...amper classed EIS 180 in accordance to the European Standard EN 13501 3 and certified CE according to EN 15650 series FOK EIS 180 MFS230V dim 500 x 300 Operated by means of a motorized operating devic...

Страница 11: ...615 0 209 6 0 525 5 1 0 5 0 358 0 410 0 75 0 444 0 399 0 4 2 5 0 495 0 59 0 270 3 75 0 480 0 58 0 303 3 0 470 800 0 855 9 5 0 088 700 0 865 10 25 0 077 600 0 845 8 75 0 1 900 1000 0 830 8 0 111 Dpt P...

Страница 12: ...3500 6500 8000 4 5 6 7 8 9 0 4 0 2 Kr 1 0 8 0 6 10 2 35 40 45 50 L wa1 dB A 1 1 5 3 4 2 Vf m s 1 5 2 3 4 5 6 7 8 9 10 0 15 0 02 DPt Pa 30 15 20 10 100 60 80 40 0 06 0 05 0 03 0 04 0 08 0 1 0 8 A free...