INSTALLATION
1. Operating device position
- RIGID WALL
8
01/19
nominal
+ 1
50
H
nominal
+ 1
50
±20
±20
0º
180º
2. Support construction opening
4 .Sealing
Sealing: Mortar
DETAIL A
A
3. Starting plane of supporting construction
144
Starting plane of supporting construction/ sealing
Dimensions
Supporting construction
Sealing
Classification
200 x 200 to 1000 x 600
Rigid wall
Brick wall
≥ 110mm
Mortar
EI180 (v
e
i
↔o) S (300Pa)
200 x 200 to 1000 x 600
Rigid wall
Reinforced concrete
≥ 110mm
Mortar
EI180 (v
e
i
↔o) S (300Pa)
>1000 x 600 to 1500 x 800
Rigid wall
Brick wall
≥ 150mm
Mortar
EI180 (v
e
i
↔o) S (500Pa)
>1000 x 600 to 1500 x 800
Rigid wall
Reinforced concrete
≥ 150mm
Mortar
EI180 (v
e
i
↔o) S (500Pa)