Fig. 64: Dry mortarless installation remote from a lightweight partition wall with wall penetration, on two sides with
installation kit WE / WE2
1
FKRS-EU
2.6
Installation kit WE / WE2
3.1
Solid wall
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
4.1
Solid ceiling slab
6.13
Mineral wool,
≥
1000 °C or gypsum mortar for
compensating unevenness
9.4
Sheet steel duct with fire-rated cladding and sus-
pension system according to Promat® manual,
construction 478, latest edition
9.5
Suspension system (by others) consisting of:
a
Threaded rod M10
b
Hilti
®
mounting rail MQ 41
×
3 mm or equivalent
c
Hilti
®
drilled plate, MQZ L13 or equivalent
d
Hexagon nut M10 with washer
Up to EI 90 S
Additional requirements: dry mortarless installation with installation kit WE / WE2 remote from lightweight
partition walls with wall penetration
Lightweight partition wall or compartment wall, see
Installation kit WE / WE2, see
Sheet steel ducts without any openings, with fire-resistant cladding (fittings with cladding according to instruc-
tions from Promat®)
≥
300 mm distance between two fire dampers
Note:
For more installation details and for components to be provided by others, see the WE / WE2 installation
manual.
Installation
Lightweight partition walls and compartment wall... > Installation with installation kit WE / WE2 re...
Fire damper Type FKRS-EU
80