5.10 Sandwich panel walls
5.10.1
Dry mortarless installation
Fig. 106: Dry mortarless installation into sandwich panel wall
1
FKRS-EU
2.17
Fire protection block Hilti CFS-BL
3.12
Sandwich panel wall 100 – 200 mm, with mineral
wool filling
≥
1000 °C,
≥
150 kg/m³, sheet metal
thickness
≥
0.5 mm on both sides
6.10
Ablative coating thickness = min. 2.5 mm, around
the perimeter
6.19
Mineral wool,
≥
1000 °C,
≥
80 kg/m³, around the
perimeter,
Leave out the actuator and release mechanisms;
inspection openings must be accessible
6.20
Sleeve (can be ordered separately)
6.24
Panel insulating material
≥
6 mm, Armaflex AF /
Armaflex Ultima, alternatively panel insulation
made of elastomeric foam (flame-resistant, non-
dripping)
The following applies in Germany: For notes on
the use of elastomeric foams, see
7.1
Trim panels 100 – 200 mm, alternatively UW sec-
tion
9.2
Extension piece or duct
*
6.19, 6.20 or 6.24 as an alternative