INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR DAMPERS AND OUTDOOR AIR

HOOD USED WITH 156-300S UNITS

507214-04
2/2019
Supersedes 507214-03

©

2019

OUTDOOR AIR DAMPERS

OUTDOOR AIR DAMPERS

Shipping and Packing List

13U04 Motorized Outdoor Air Damper
Package 1 of 1 contains:

 1- Outdoor air damper (OAD) assembly

 1- Bag assembly containing:

2-Wiring diagram D sections
1-P160 wiring harness

Outdoor air hood parts (same as 13U05 hood parts

except there are NOT two manual damper blades)

13U05 Manual Outdoor Air Damper
Package 1 of 1 contains:

 2- Manual damper blades

Outdoor air hood parts*

1-Hood top

1-Bottom filter bracket

2-Front filter brackets

2-Hood sides

2-Filters

Bag assembly containing:

46-Self drilling screws

*When outdoor air assembly is factory-installed,
outdoor air hood parts are packaged separately and
shipped in the filter compartment. See figure 1.

WARNING

Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier

CAUTION

As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in­
jury. Take care while handling this equipment and
wear gloves and protective clothing.

Application

Optional outdoor air dampers provide fresh outdoor air.

See table 1 for usage.

C1DAMP20C-1 Motorized Dampers:

Electro-mechanical units (no Unit Controller)-

The damper opens to a set position when the blower is

operating. To operate the damper only during the

occupied time period, an optional thermostat or energy

management system must be installed that provides an

occupied signal to the unit's thermostat connection.

Units equipped with an A55 Unit Controller-

The damper opens to a set position when the blower is

operating and an occupied signal is provided to the Unit

Controller

C1DAMP10C-1 Manual Damper:

Damper is manually operated; damper position is

manually set at installation and remains in that position.

Install Motorized Damper - C1DAMP20C-1

1- Disconnect all power to unit and open filter access

panel.

2- If damper is factory-installed, remove six screws

securing hood top to access panel. See figure 2. Retain
hood top and go to the 

Outdoor Air Hood

 section.

3- Remove and retain sheet metal screws securing

cover plate to the top rear access panel. Discard
cover plate. See figure 3.

TABLE 1

Damper Type

Unit

Model #

Part #

Cat. #

Motorized

156-300S

C1DAMP20C-1

613924-01

13U04

Manual

156-300S

C1DAMP10C-1

613924-02

13U05

Содержание C1DAMP20C-1

Страница 1: ...act with sharp sheet metal edges can result in personal in jury Take care while handling this equipment and wear gloves and protective clothing Application Optional outdoor air dampers provide fresh o...

Страница 2: ...ng where the cover plate was secured See figure 5 Secure with retained screws 6 From inside the filter access panel remove the unit jumper plug P3 from unit jack J3 and discard See figure 6 7 Units eq...

Страница 3: ...ON OUTDOOR AIR DAMPER ASSEMBLY COVER PLATE OPENING FIGURE 6 DISCARD P3 JUMPER PLUG J3 UNIT JACK REMOVE AND DISCARD P3 JUMPER PLUG FIGURE 7 WIRING UNITS EQUIPPED WITH A UNIT CONTROLLER CONNECT P4 MOTOR...

Страница 4: ...e two screws securing dampers in place for shipping See figure 9 6 To adjust manual damper outdoor air amount loosen the slots screws and slide dampers to the desired position Tighten the screws to se...

Страница 5: ...s See figure 10 5 Secure the hood top to the left and right hood sides Tighten the previously installed screws FIGURE 11 HOOD SIDE VIEW ALIGN VERTICAL HOLES ON BRACKET WITH VERTICAL HOLES ON SIDE OF H...

Страница 6: ...mperature Mark that point on the top line of chart 1 and label point C 70 F 21 C shown 4 Draw a straight line between points A and B 5 Draw a vertical line through point C 6 Draw a horizontal line whe...

Страница 7: ...enu paths to set the low speed minimum damper position M3 Unit Controller SETUP TEST BALANCE DAMPER MIN DAMPER POSITION BLOWER ON LOW M2 Unit Controller SETTINGS SETPOINTS DAMPER MIN OCP BLOWER LOW 5...

Страница 8: ...eed pressure differential in table 2 3 Read the damper percentage open Units Equipped With Unit Controller The damper percentage open was entered into the Unit Controller Units Not Equipped With Unit...

Отзывы: