background image

Page 2

FIGURE 1

FACTORY-INSTALLED HOOD PARTS LOCATION

ADDITIONAL

HOOD PARTS IN

CARTON

BOTTOM FILTER

BRACKET

REMOVE TWO

SCREWS RETAINING

BOTTOM FILTER

BRACKET

Install Motorized Damper - C1DAMP20C-1

Continued

FIGURE 2

HOOD TOP

REMOVE HOOD TOP - FACTORY-INSTALLED OAD

TOP REAR

ACCESS PANEL

FILTER ACCESS

PANEL

FIGURE 3

FIELD-INSTALLED OAD

TOP REAR

ACCESS

PANEL

FILTER ACCESS

PANEL

DISCARD

COVER

PLATE

4-

Units NOT equipped with an A55 Unit Controller -

Open the DIP switch access cover on the damper
motor and adjust the setting. See figure 4.

5- Install damper assembly into top rear access opening

where the cover plate was secured. See figure 5.
Secure with retained screws.

6- From inside the filter access panel, remove the unit

jumper plug P3 from unit jack J3 and discard. See
figure 6.

7-

Units equipped with an A55 Unit Controller -
C

onnect damper motor plug P4 to unit jack J3.

Discard P160 jumper harness included in the field kit.

8-

Units NOT equipped with an A55 Unit Controller -
C

onnect the kit jumper harness plug P160 to unit jack

J3 and jumper jack J160 to the damper motor plug
P4. See figure 7.

9- Close the filter access panel.

10- Install the applicable wiring diagram in the control

compartment; discard the other diagram. Units
equipped with an A55 Unit Controller use the diagram
showing A55 in the key list. Units NOT equipped with
an A55 Unit Controller use the other diagram.

Содержание C1DAMP20C-1

Страница 1: ...act with sharp sheet metal edges can result in personal in jury Take care while handling this equipment and wear gloves and protective clothing Application Optional outdoor air dampers provide fresh o...

Страница 2: ...ng where the cover plate was secured See figure 5 Secure with retained screws 6 From inside the filter access panel remove the unit jumper plug P3 from unit jack J3 and discard See figure 6 7 Units eq...

Страница 3: ...ON OUTDOOR AIR DAMPER ASSEMBLY COVER PLATE OPENING FIGURE 6 DISCARD P3 JUMPER PLUG J3 UNIT JACK REMOVE AND DISCARD P3 JUMPER PLUG FIGURE 7 WIRING UNITS EQUIPPED WITH A UNIT CONTROLLER CONNECT P4 MOTOR...

Страница 4: ...e two screws securing dampers in place for shipping See figure 9 6 To adjust manual damper outdoor air amount loosen the slots screws and slide dampers to the desired position Tighten the screws to se...

Страница 5: ...s See figure 10 5 Secure the hood top to the left and right hood sides Tighten the previously installed screws FIGURE 11 HOOD SIDE VIEW ALIGN VERTICAL HOLES ON BRACKET WITH VERTICAL HOLES ON SIDE OF H...

Страница 6: ...mperature Mark that point on the top line of chart 1 and label point C 70 F 21 C shown 4 Draw a straight line between points A and B 5 Draw a vertical line through point C 6 Draw a horizontal line whe...

Страница 7: ...enu paths to set the low speed minimum damper position M3 Unit Controller SETUP TEST BALANCE DAMPER MIN DAMPER POSITION BLOWER ON LOW M2 Unit Controller SETTINGS SETPOINTS DAMPER MIN OCP BLOWER LOW 5...

Страница 8: ...eed pressure differential in table 2 3 Read the damper percentage open Units Equipped With Unit Controller The damper percentage open was entered into the Unit Controller Units Not Equipped With Unit...