Fig. 60: Dry mortarless installation with installation kit TQ / TQ2 into a lightweight partition wall, below a flexible
ceiling joint
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
4.1
Solid ceiling slab
5.1
Dry wall screw
6.5
Mineral wool (depending on wall construction)
6.13
Mineral wool strips A1, if required, alternatively
gypsum mortar
7.1
UW section
7.10
Trim panels
7.21
Ceiling joint strips (e.g. 4
×
≥
10 mm)
#
according to installation details Fig. 57 to Fig. 59
Up to EI 90 S
Note:
representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the
expected ceiling subsidence and the specifications of the wall manufacturer.
Additional requirements: dry mortarless installation with installation kit TQ / TQ2 into lightweight partition
walls
Lightweight partition wall or compartment wall, see
Installation kit TQ / TQ2, see
≥
200 mm distance between two fire dampers in separate installation openings
Installation
Lightweight partition walls and compartment wall... > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
76