5.3.1.3
Installation kit TQ / TQ2
Installation kit TQ / TQ2 for dry mortarless installation into walls
The installation kit TQ is an integral component of the fire damper and must be ordered together with the
damper.
The installation kit TQ2 is supplied separately and must be installed by the customer.
The installation kit can also be supplied subsequently and mounted on the fire damper.
Fig. 23: Supply package and installation of installation kit TQ2 for dry mortarless installation
1
FKRS-EU
2.11
Installation kit TQ2, consisting of:
a
Half-shell 1
b
Half-shell 2
c
Bracket
d
Intumescent seal (2 strips)
Installation of installation kit TQ2
1.
Lay half-shells (2.11a) and (2.11b) of the installation kit (2.11) around the FKRS-EU and fix with two brackets
(2.11c) (installation position of the FKRS-EU as required).
2.
Affix intumescent seal (2.11d).
Installation
General installation information > Installation block and installation kits
Fire damper Type FKRS-EU
36
Содержание FKRS-EU
Страница 176: ...Fire damper Type FKRS EU 176...