Interval
Measure
Staff
C
Cleaning the fire damper
No contamination in the interior or on the exterior of the fire damper
No corrosion
–
Remove contamination with a damp cloth
–
Remove corrosion or replace part
Specialist per-
sonnel
Function of limit switches
Function OK
–
Replace the limit switches
Specialist per-
sonnel
Function of the external signalling (damper blade position indicator)
Function OK
–
Determine and eliminate the cause of the fault
Specialist per-
sonnel
Interval
A = Commissioning
B = Regularly
The functional reliability of fire dampers must be tested at least every six months. If two consecutive tests are
successful, the next test can be conducted one year later. The function of fire dampers with a spring return
actuator can also be tested with an automatic control unit (remote controlled). The system owner can then
set the intervals for local tests.
C = as required
Item to be checked
Required condition
–
Remedial action if necessary
Maintenance
Inspection, maintenance and repair measures
Fire damper Type FKRS-EU