5.4.6 Dry mortarless installation with installation kit TQ / TQ2
Fig. 35: Dry mortarless installation with installation kit TQ / TQ2
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
3.1
Solid wall
5.7
Anchor bolt Hilti
®
HUS-6 or equivalent, appropriate
for the wall material, alternatively push through
installation
Up to EI 120 S
Additional requirements: dry mortarless installation with installation kit TQ / TQ2 into solid walls
Solid wall
Installation kit TQ / TQ2, see
≥
75 mm distance from fire damper to load-bearing structural elements
≥
200 mm distance between two fire dampers
1.
Make a square installation opening, size
Æ
DN + 110 mm
2.
Position the fire damper with the installation kit in the centre of the installation opening and push it in up to the
cover plate.
If the wall thickness is >115 mm, extend the fire damper on the installation side with an extension piece or a
spiral duct.
3.
Fix the cover plate with four threaded rods (push through installation) or with at least four M6 screws. Screw
fixings in solid walls must be made using tested anchors appropriate for the construction material of the partic-
ular wall.
Installation
Solid walls > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
47