5.11.11 Installation with installation kit WE / WE2 remote from solid ceiling slabs
Fig. 122: Dry mortarless installation with installation kit WE / WE2, remote from a solid ceiling slab
1
FKRS-EU
2.1
Mortar
2.6
Installation kit WE / WE2
4.1
Solid ceiling slab
5.1a
Dry wall screw, 4
×
50 mm
5.1b
Dry wall screw, 4
×
30 mm
5.7
Anchor bolt Hilti
®
HUS-6 or equivalent
5.9
Steel angle section 40
×
40
×
1.5 mm
6.2
Mineral wool, ≥ 1000 °C, ≥ 80 kg/m³
9.4
Sheet steel duct with fire-rated cladding and sus-
pension system according to Promat® manual,
construction 478, latest edition
9.5
Suspension system (by others) consisting of:
a
Threaded rod M10
b
Hilti
®
mounting rail MQ 41
×
3 mm or equivalent
c
Hilti
®
drilled plate, MQZ L13 or equivalent
d
Hexagon nut M10 with washer
Up to EI 90 S