5.11.6
Mortar-based installation into composite ceilings
Fig. 117: Mortar-based installation into composite ceilings, shown upright (also applicable for suspended arrange-
ment)
1
FKRS-EU
2.1
Mortar
2.2
Concrete
4.10
Reinforced composite ceiling*
7.8
Steel girder
7.27
Profile sheet metal
Up to EI 90 S
*
Illustration representative, other ceiling construc-
tions possible according to local conditions and
ceiling manufacturers
Additional requirements: mortar-based installation into composite ceilings
≥
40 mm distance from fire damper to load-bearing structural elements
≥
45 mm distance between two fire dampers
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation into composite ceili...
Fire damper Type FKRS-EU
136