5.9.1 Dry mortarless installation with installation kit TQ / TQ2
Fig. 104: Dry mortarless installation with installation kit TQ / TQ2 into a shaft wall without metal support structure
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
3.9
Shaft wall without metal support structure, clad-
ding on one side
5.1
Dry wall screw
7.1
UW section
7.10
Trim panels
7.13
Cladding, two layers
7.14
Reinforcing board of the same material as the
wall
#
optional
Up to EI 90 S
Additional requirements: dry mortarless installation with installation kit TQ / TQ2 into shaft walls without
metal support structure
Installation kit TQ / TQ2, see
≥
200 mm distance between two fire dampers in separate installation openings
Approx. 100 mm distance from the fire damper to load-bearing / adjacent structural elements
Installation
Shaft walls without metal support structure > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
122