Fig. 73: Lightweight partition wall, half-timbered construction with cladding on both sides
5.1
Dry wall screw
6.8
Infill*
7.9
Half-timbered construction
7.11
Trim panels, double layer, staggered joints
7.13
Cladding
*
Cavities completely filled with mineral wool
≥
50 kg/m³, bricks, aerated concrete, lightweight
concrete, reinforced concrete or clay
☐
A
Clear installation opening
☐
A1
Opening in the half-timbered construction,
☐
A1 =
☐
A + (4
×
trim panels)
Additional requirements: lightweight partition walls with timber support structure / half-timbered construc-
tion
Timber support structure or half-timbered construction, see
Installation opening A [mm]
Installation type
Nominal size
100
125
150
160
180
200
224
250
280
315
Mortar-based installation
☐
A =
Æ
DN + max. 450 mm
Dry mortarless installation with installation
kit TQ / TQ2
1
☐
A =
Æ
DN + 110 mm
Dry mortarless installation with fire batt
☐
A =
Æ
DN + 80 – 1200 mm
1)
Installation opening tolerance
±
2 mm
Installation
Lightweight partition walls with timber support ... > Dry mortarless installation with fire batt
Fire damper Type FKRS-EU
90