5.9 Shaft walls without metal support structure
Fig. 103: Shaft wall without metal support structure and with cladding on one side
5.1
Dry wall screw
5.6
Screw or steel rivet
7.1
UW section
7.1a
UW section, cut in and bent or cut off
7.2
CW section
7.13
Double layer cladding, on one side of the metal
stud system
7.14
Reinforcing board
*
Closed side of metal section must face the instal-
lation opening
☐
A
Clear installation opening
Additional requirements: shaft walls without metal support structure
Shaft wall without metal support structure, see
Installation opening A [mm]
Installation type
Nominal size
100
125
150
160
180
200
224
250
280
315
Dry mortarless installation with installation
kit TQ / TQ2
1
☐
A =
Æ
DN + 110 mm
Dry mortarless installation with installation
kit WA / WA2
Æ
DN + approx. 5 mm
1)
Installation opening tolerance
±
2 mm
Installation
Shaft walls without metal support structure > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
121
Содержание FKRS-EU
Страница 176: ...Fire damper Type FKRS EU 176...