Installation
5.1 Installation situations
Note
The performance classes of the fire damper and the wall or ceiling slab may differ. The lower performance class
determines the performance class of the overall system.
Installation situations
Supporting con-
struction
Installation location
Minimum
thickness
[mm]
Class of per-
formance EI TT
(v
e
–h
o
, i ↔ o) S
up to
Installation
type
Installa-
tion
informa-
tion
Solid walls
in
100
EI 120 S
N
100
EI 90 S
N
in, combined assembly
100
EI 90 S
N
in, multiple mounting
100
EI 90 S
N
in, partly with mineral wool
100
EI 120 S
N
in, underneath flexible ceiling
joint
100
EI 90 S
N
in, installation block ER
100
EI 90 S
E
in, installation kit TQ / TQ2
100
EI 120 S
E
on the face of, installation kit
WA / WA2
100
EI 90 S
E
remote from, wall attachment,
installation kit WE / WE2
100
EI 120 S
E
remote from, wall penetration,
installation kit WE / WE2
100
EI 120 S
E
remote from, mineral wool insu-
lation
100
EI 60 S
T
in, fire batt
100
EI 120 S
W
1
100
EI 90 S
W
1
in, combined penetration seal
100
EI 90 S
W
1
in, fire protection block bulk-
head
100
EI 90 S
T
Metal stud walls
in
94
EI 120 S
N
1
94
EI 90 S
N
1
80
EI 60 S
N
1
75
EI 30 S
N
1
1)
The class of performance depends on the installation details
2)
Thickness increased near the installation opening
3)
Cadolto system
4)
Depending on local conditions
N = Mortar-based installation
E = Installation kit
W = Fire batt
E = Dry mortarless installation
Installation
Installation situations
Fire damper Type FKRS-EU
18