background image

Содержание FDMR

Страница 1: ......

Страница 2: ...ol min density 140 kg m 4 Fire protection mastic min thickness 1 mm 50 25 4 Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT Fire resistant...

Страница 3: ...LTI CFS CT 4 HILTI CFS CT 5 HILTI CFS S ACR Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material...

Страница 4: ...sity 140 kg m 4 Fire protection mastic min thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 1...

Страница 5: ...5 100 100 100 Position 1 Fire damper 2 Installation frame 3 Solid wall construction 100...

Страница 6: ...ckness 1 mm 5 Duct Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for dampe...

Страница 7: ...to EN 1366 1 2014 must be used Used materials example 4 DN 100 DN 800 System ISOVER_ULTIMATE PROTECT th 100 mm EIS 60 DN 100 DN 315 System ISOVER_ULTIMATE PROTECT th 120 mm 2x60 mm EIS 90 DN 350 DN 80...

Страница 8: ...thickness 1 mm 5 Cement lime plate min thickness 15 mm min density 870 kg m 6 Stone wool with one side stitched wire fencing min density 105 kg m thickness 180 mm e g 3x60 mm 7 Stone wool with one si...

Страница 9: ...40 50 5 Promastop P K Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material propertie...

Страница 10: ...ystem for damper installation with equivalent material properties 40 40 50 40 100 Used materials example 4 HILTI CFS F FX EIS 60 PROMAFOAM C EIS 45 SOUDAL Soudafoam FR B1 EIS 30 DenBraven Fire protect...

Страница 11: ...s 1 mm 6 Cement lime plate min th 15 mm min density 870 kg m 7 Duct Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 5 Promatect H Fire resi...

Страница 12: ...een screws 200 mm Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm Installation opening has to be r...

Страница 13: ...FS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties...

Страница 14: ...ting th 1 mm 7 Duct D 60 to 800 max 2050 Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT 110 D 60 to 800 max 1650 Fire resistant insulation and fire resistant board can be replaced by...

Страница 15: ...wool type depending on the type of construction 4 Mortar or gypsum 5 Stone wool with wired mat on one side density 66 kg m 6 Duct Installation opening has to be reinforced by profile UW CW Profil is...

Страница 16: ...me plate min thickness 15 mm min density 870 kg m 7 Stone wool with one side stitched wire fencing min density 105 kg m thickness 180 mm e g 3x60 mm 8 Stone wool with one side stitched wire fencing mi...

Страница 17: ...istant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties 25 50 Position 1 Fire damper 2 Solid ceil...

Страница 18: ...Promatect H Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties Position 1 Fire dampe...

Страница 19: ...d fire resistant board can be replaced by another approved fire sealing system for damper installation with equivalent material properties Position 1 Fire damper 2 Solid ceiling construction 3 Stuffin...

Страница 20: ...20 Position 1 Fire damper 2 Installation frame 3 Solid ceiling construction min 110 Concrete min 125 Aerated concrete...

Страница 21: ...t Used materials example 3 Hilti CFS CT B 1S 140 50 4 Hilti CFS CT Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper installation wi...

Страница 22: ...nt material properties Depends on the distance of the flap from the construction when the maximum distance from the construct is not limited and according to EN 15882 2 must use the required number of...

Страница 23: ...density 105 kg m thickness 60 mm 6 Duct min 110 Concrete min 125 Aerated concrete 100 400 variable 40 180 240 Stuffing box fire protection mastic cement lime plate and insulation materials can be repl...

Страница 24: ...24 Position 1 Fire damper 2 Solid ceiling construction 3 Concrete B20 4 Rebar 5 Duct Around the perimeter min 110 Concrete min 125 Aerated concrete 30 100 50 100 100 750...

Страница 25: ...20 D 300 50 50 130 130 110 400 Position 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera 300 50 120 D 110 400 180 50 300 50 120 50 D 110 136 400...

Страница 26: ...26 Position 1 Damper casing 2 Mechanics 3 Damper blade 4 Inspection hole covering 5 Sensor sticker 6 Hole for camera 400 110 180 D 120 400 D 110 136 39 120 400 130 130 110 D 120...

Страница 27: ...ing mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole for camera X 53 mm BFL X 72 mm BFN X 78 mm BF 300 50 X 110 400 180 50 D 300 50 50 D 110 136 400...

Страница 28: ...DN 355 DN 400 X 72 mm BFN X 78 mm BF Position 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical starting mechanism 6 Hole for camera 400 X 110 180...

Страница 29: ...or 5 Mounting plate 6 Mechanics 7 Thermal fuse 1 Damper 2 Mounting plate 3 Actuating mechanism 4 Temperature sensor 5 Mounting plate 6 Mechanics 7 Thermal fuse 8 Sensor sticker 9 Hole for temperature...

Страница 30: ...ween the adjacent dampers must be at least 200 mm The damper blade in its closed position must be inside of the fire separating structure The fire damper may also be installed outside the wall structu...

Страница 31: ...damper control parts At least one inspection hole must be accessible The damper body must not get deformed during its installation process Once the damper is built installed its blade must not grind o...

Страница 32: ...5 80 BAT Tf Tf LED 1 2 S3 S1 S2 S5 S4 S6 N L1 5 80 BAT Tf Tf LED AC 230V 5A IP 67 25 C 120 C 1 COM black wire 2 NC gray wire 4 NO blue wire This limit switch is possible to connect in following two ve...

Страница 33: ...fuse from the fuse holder of initiation device check its correct functionality The mechanism is identified as M1 to M5 depending on the closing spring strongness The actuator design must be checked a...

Страница 34: ...stos free fire resistant mineral fibre boards The damper control devices are made of galvanized materials alternatively of stainless steel without any additional surface finish The springs are galvani...

Страница 35: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Отзывы: