Installation opening A [mm]
Installation type
Nominal size
100
125
150
160
180
200
224
250
280
315
Mortar-based installation
1
☐
A =
Æ
DN + max. 450 mm
Dry mortarless installation with installation
kit TQ / TQ2
1, 2
☐
A =
Æ
DN + 110 mm
Dry mortarless installation with fire batt
☐
A =
Æ
DN + 80 – 1200 mm
1)
Trim panels, according to installation details
2)
Installation opening tolerance
±
2 mm
Additional requirements: lightweight partition walls and compartment walls with metal support structure
Lightweight partition wall or compartment wall, see
Erecting a wall and creating an installation opening
Erect the lightweight partition wall according to the manufacturer's instructions and create an installation
ff
–
Option 1: Provide the installation opening in the metal support structure with suitable metal sections, then
clad the wall.
–
Option 2: After cladding the wall, create a square wall opening (clear installation opening
≤
475 mm)
between the regular studs and brace it with a perimeter metal section. Screw metal sections onto both sides
over the cladding, spaced approx. 100 mm apart.
Installation
Lightweight partition walls and compartment wall... > Dry mortarless installation with fire batt
Fire damper Type FKRS-EU
66